Configure

630A CB with VIP400 protection + metering
Gear type | Extensible Breaker with Metering | |
Enclosure | IP54 (Indoor/Outdoor) | |
Service Voltage | 12KV | |
Interrupting Capacity | 21ka | |
Normal Current Rating | 630A | |
Busbars Rating | 630A | |
BIL/kV | 95kV | |
Operating Mechanism | Independent Manual | |
Protection CTs | 800/1A class X | |
Protection - relay | VIP 400 | |
Metering | PM5110 | |
Metering CTs | 400/200/5A | |
VTs | 12kV/120V |